B. System Specifications
ENVIRONMENTAL
Temperature -10F to +12OF
Humidity 90% RH, Non-condensing
Surge 2500 V, Per ANSI
C37-90A-1974, common and
differential mode
EMI/RFI per FCC part 15C
ELECTRICAL
Power requirements 120 VAC, 50/60 Hz, 7 watts
Fault sensing current Less then 10 mA per channel
Battery Backup 4 hours typical
Power outage detection time 1-99 seconds
PHYSICAL
Dimensions 11 5/8 x 9 7/16 x 4 inches
Weight 10 lbs.
Mounting method Flange mount, 4 points
Enclosure NEMA 12 std., others optional
TELEPHONE SYSTEM
FCC registered for direct interconnect FCC Registration Number:
D4J6M6-13598-AL-E
Dialing capacity 8 numbers, 16 digits each,
maximum
Dialing format Loop disconnect, 10 pps
nominal; or tone,
100ms/100ms; user
selectable
Answer delay Programmable, 1 to 99 rings
Acknowledged intercall delay Programmable, 1 to 99 hours
Unacknowledged intercall delay One Minute
Surge and environmental protection Per FCC part 68
OPERATIONAL
Fault detection method Normally open or closed,
selectable
Fault integration time constant One to 99 seconds
Station identification Name or number, user selectable
user programmable messages
Message repetitions One to 99, user programmable
Data retention Nonvolatile EEPROM
Programming Local keyboard entry
20